NDB2Z-63

未分类 8120
NDB2Z-63(images 1)

1、Applicable scope and purpose

●Short -circuit protection

●Over-load protection

●Control

●Isolation

●DC system protection

NDB2Z-63 dedicated to the low voltage power distribution system of industrial, buildings, energy communications and infrastructure.

1P 2P

2、Model and implication:

NDB2Z-63(images 2)

3、Main technical specification

●Electrical parameters

○Rated working voltage and relevant breaking capacity:

Pole1P2P  certificate 
 Rating current(A)1A, 1.2 A, 1.5 A, 1.6 A, 2A, 3A, 4A, 5A, 6A, 7A, 8A, 10A, 12A,13A, 15A, 16A, 20A, 25A,30A,32A, 40A, 50A, 60A, 63A 
ItemIcu 
  VoltageDC125V10kA/ CCC CE/TUV 
DC220V/250V10kA/ 
DC250V/10kA 
DC440V/500V/10kA 
 
  VoltageDC125V10kA, U1/  UL1077
DC220V4.5 kA, U1/
DC250V/10kA, U1
DC440V/4.5 kA, U1
○Impulse withstand test voltages: 4kV
○electrical endurance: 1500 times;Mechanical endurance: 20000 times
Product certification and implementation standard.:
○Product certificate:CCC,CE,TUV,UL1077;
○Product certification standard:GB/T 14048.2,IEC60947-2,UL1077;
Environmental requirements:RoHS
Isolation function
○Practical breaking instructions
○View window within the green identification said contact in the off position
Tripping characteristic B type curve
Protection of short circuit current small load
rated current:1A~63A
tripping characteristic:The instantaneous tripping range 6In(1±20%)
 
C type curve
Protect normal load and distribution wire cable
rated current:1A~63A
tripping characteristic:The instantaneous tripping range 12In(1±20%)
●Wiring diagram:
NDB2Z-63(images 3)
NDB2Z-63(images 4)

1P 2P

4、Normal working environment

●Ambient temperature:-40℃~+70℃

●Air relative humidity:≤95%

●Altitude:≤2000m

●pollution degree: 3

●Service place without significant vibration and impact

●Lower capacity coefflcient table above 2000 meters above sealevel

NDB2Z-63(images 5)

●Side-by-side volume reduction coefflcient table

NDB2Z-63(images 6)

●Temperature Derating Parameter Table:

NDB2Z-63(images 7)

5、Tripping characteristic

NDB2Z-63(images 8)
NDB2Z-63(images 9)

6、Outline dimensions

NDB2Z-63(images 10)

1P

NDB2Z-63(images 11)

2P

7、Mounting

Modular construction,can be installed in EN60715 TH 35mm x 7.5mm standard guide rail.

8、Connect line requirements

  • Standard cross-sections of round copper conductors: 1~35mm2
    • Terminal screw: M5 ,Rated torque : 2.0N.m

9、Packing storage

Quantity(1P product:12 PCS/box,2P product:6PCS/box),Packing boxes of products should be stored in the air circulation and relative humidity is not more than 80% and the temperature is not higher than +       70 ℃,Not less than – 40 ℃ in the air around without acid, alkali or other corrosive gases stored in the warehouse. In the above conditions, the storage period since the production date not more than three years.

10、Accessories list and mounting

●OF2 auxiliary contacts Installed on the left hand of the NDB2Z – 63 circuit breaker left, indication circuit breaker on-off state;

●SD2 indicator contacts Installed on the left hand of NDB2 Z – 63 circuit breaker , indication failure tripping status of breaker;

●MX+OF2 shunt trip release Installed on the left hand of NDB2 Z – 63 circuit breaker, remote control of the circuit breaker’s tripping;

11、 Notice

1、Customers who disassemble the product without approval shall undertake relevant quality problems by themselves;

2、 Do not touch the naked part of conductive components when the product is power on;

3、Don’t test characteristics of the breaker optionally, the manufacturer is irresponsible for such quality problems;

4、Keep wiring correct to prevent malfunction or damage of wiring terminals.

5、Please open the cover when installing the accessory. Please refer to OF2, SD2, MX+OF2 Instruction for details.

LAST:

Ähnliche Empfehlungen

  • NDB2LE-25

    690

    1、Application Scope and Purpose The NDB2LE-25 series of residual current action circuit breakers provide the ground leakage, direct or indirect electric shock by human body and othe...

    Details anzeigen
  • NDM2L-630

    581

    1.Applicable Scope and Purpose of Circuit BreakerThe NDM2L-630 molded case circuit breaker with the residual current protection (hereinafter referred to as circuit breaker) applies to infrequent switching of circuits with the AC 50/60Hz, the worki...

    Details anzeigen
  • NDB2LE-63

    635

    ●Protection against short circuit ●Protection against overload ●earth leakage Protection ●Isolation NDB2LE-63 series residual current unit clipped onto the right side of NDB2-63 series MCBs to protection against earth ...

    Details anzeigen
  • NDB2LM-40

    594

    1、Application The NDB2LM-40 series of residual current action circuit breakers (RCBO) are applicable to the domestic and similar places and some places with a high sensitivity, which are also applicable to laboratories, service industries and sma...

    Details anzeigen
Mehr erfahren!

Liste der Beratungsangebote
Liste der Beratungsangebote Anfrage zu den oben genannten Produkten senden