The NDB2LE-25 series of residual current action circuit breakers provide the ground leakage, direct or indirect electric shock by human body and other faults protection, which are applicable to the low-voltage terminal distribution in the industry, civil buildings, energy, communication, infrastructure and other fields.
2、Model and implication
3、Main technical parameters
Electrical parameters
Rated working voltage: AC230V/240V
Frequency: 50/60Hz
Rated woring current: 6A, 10A, 16A, 20A, 25A
Rated breaking capacity: 6kA
Rated impulse withstand voltage: 4kV
Rated residual operating current: 30mA
Rated insulation voltage: 500V
Type of the residual tripping current: Type AC
Mechancal life: 20,000 times
Electrical life: 60,00 times
Isolating function
Switch on and off instructions
The green mark in the inspection window indicates that the contact is in disconnected position
Tripping characteristics: Range of instantaneous tripping 5In~10In
C curve(5~10)In
6、Outline and installation dimensions
7、Installation method
It can be easily installed on the TH35mm×7.5 standard guide
8、Packaging and storage
Maximum packaging quantity are 12 pieces/box. The packaged products should be stored in a warehouse with the air ventilation and the relative humidity no more than 80% and the temperature between -30℃ and +70℃. No acidic, alkaline or other corrosive gas exists in the ambient air in the warehouse. Under the above conditions, the storage period shall be no more than three years since the manufacturing date.
9、Environment
●Comply with the requirements of RoHS directives.
10、Accessory list and installation
No 12、Notices
The user must be responsible for product issue that occurs because the user disassembles the product without approval;
It fails to provide protection for the electric shock caused due to two phases of the contacted lines to be protected;
Do not test the insulation resistance of the product or carry out power frequency withstand voltage tests directly or indirectly with a megger or similar devices on the product so as to avoid damage to the product. If required by users, our company can provide an effective proof of the conformance test;
In case of insulation resistance test on the project line, do not connect the product so as to avoid
misunderstanding of the product quality or damage to the circuit board;
Wiring of the leakage circuit breaker shall be done according to the up-in and down-out principle. Do not wire it wrongly. Otherwise, it may damage the product by pressing the test button again or in case of current leakage in the line;
Wiring must be reliable to prevent the malfunction of the leakage circuit breaker or terminal burning damage due to the abnormal heat generation on the terminal;
Carry out a monthly stimulated test on the current leakage. Namely, press the test button to make the circuit breaker act so as to test proper operation of the circuit breaker, and replace the abnormal products in a timely manner;
For automatic disconnection of the leakage circuit breaker, analyze fault reasons for the line or equipment.
1. Applicable Scope and Purpose of Circuit Breaker The NDM2L-400 molded case circuit breaker with the residual current protection (hereinafter referred to as circuit breaker) applies to infrequent switching of circuits with the AC 50/60Hz, the wor...
The NDB2LE-40 series of residual current action circuit breakers provide the ground leakage, direct or indirect electric shock by human body and other faults protection, wh...
●Protection against short circuit ●Protection against overload ●earth leakage Protection ●Isolation NDB2LE-63 series residual current unit clipped onto the right side of NDB2-63 series MCBs to protection against earth ...