The NDM5-1600 series of moulded case circuit breakers (referred to as circuit breakers) have a rated insulation voltage of 1000V and apply to circuits with the AC 50Hz/60Hz, the rated working voltageAC380/400/415V、AC500V、AC660/690V、AC800V,Vand rated working current (800A to 1250A). The circuit breakers are used for distributing power while protect the overload, short circuit and under-voltage (with a under-voltage release) of lines and power units as well as the infrequent starting, braking, overload and short circuit of motors.
Each voltage level and short-circuit section capacity of the circuit breaker can be connected with the lower incoming line.(Except AC800V )

Technical Parameters

ModleNDM5-1600
Frame current Inm(A)1600
Rated voltage Ue(V)AC380/400/415、500、660/690、800
Rated current In(A)800、1000、1250
Rated insulation voltage Ui V)1000
Power frequency withstand voltage(V)3500
Rated impulse withstand voltage Uimp(kV)12
Number of poles33、43
Interrupting level codeLMH
Rated      limit short-circuit breaking capacity Icu (kA)AC380/400/415V70100100
AC500V507085
AC660/690V203550
AC800V//30
Rated operating short-circuit breaking capacity Ies (kA)AC380/400/415V70100100
AC500V507070
AC660/690V203542
AC800V//20
Usage categoryA
            Operational performance (times)  Mechanical lifeMaintainable free life  10000(3P)/6000(4P)
Maintainable life20000(3P)/12000(4P)
      Electrical lifeAC415V3000
AC500V1500
AC690V1000
AC800V500
BoundaryL(mm)268
NDM5-1600H Molded Case Circuit Breaker(images 2)
NDM5-1600H Molded Case Circuit Breaker(images 3)
NDM5-1600H Molded Case Circuit Breaker(images 4)
NDM5-1600H Molded Case Circuit Breaker(images 5)

Normal Working Environment of Circuit Breaker
1) The altitude of the installation site doesn’t exceed 2,500m. See the “High-altitude DeratingFactor Table of Circuit Breaker” for the derating factor at the altitude;
2) The ambient temperature is -35℃ ~ + 70℃; the average within 24 h shall not be more than+35℃. If the ambient temperature is higher than +40℃, the user needs to reduce the capacity.See the “Derating Factor Table of Temperature Change for the Circuit Breaker” for the derating factor;
3) Its relative humidity at an ambient temperature of +40℃ should not exceed 50%. A higherrelative humidity is allowed at a lower temperature. For example, the relative humidity at20℃ can reach 90%; for frost due to temperature change, the corresponding measuresshould be taken;
4) The product can withstand the effects of wet air, salt mist, oil mist and mould;
5) The installation category of the circuit breaker connected to the main loop is: Category Ⅲ (power distribution and control level), The installation category of the circuit breaker notconnected to the main loop is: Category Ⅱ (load level);
6) The pollution level is Level 3;
7) Degree of protection: IP 20;
8) The product should be installed in places that are free from explosive media, media corrosiveto metal, insulation damaging gas, and conductive dust, which should be also avoided fromsnow and rain;
9) In case of stricter user conditions than the above description, negotiate with the manufacturer.

LAST: WEITER:

Ähnliche Empfehlungen

  • NDB1L-32

    733

    NDB1L-32 is a compact RCBO for low-voltage terminal circuits. It provides overload, short-circuit and residual-current protection while allowing neutral-pole switching in a space-saving 1P+N format. Typical configuration only. Final ratings are co...

    Details anzeigen
  • NDB1LE-63 RCBO Typ B mit Überstromschutz

    851

    NDB1LE-63 type B residual current circuit breaker with overcurrent protection provide protection for sinusoidal AC residual current, pulsating DC residual current, composite residual current, and smooth DC residual current at frequencies up to 1kHz.

    Details anzeigen
  • NDC1(Z)-40 AC Contactor with AC or DC Coil

    1371

    NDC1(Z)-40 AC Contactor, which used in 50Hz(60Hz) AC circuit with the rated voltage of 1000V. It is used in AC-3 type, with the rated working voltage of 415V and rated working current of 40A, to realize distant connection and disconnection of the ...

    Details anzeigen
Mehr erfahren!

Liste der Beratungsangebote
Liste der Beratungsangebote Anfrage zu den oben genannten Produkten senden